What Wire Size for 183.33 Amps at 200 Feet?
300 kcmil copper is a typical pick for 183.33A at 200 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 300 kcmil at these inputs: 3.15V (2.62%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 183.33A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 300 kcmil sits at a branch-circuit OCP of 285A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (300 kcmil NM-B = 240A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 250 kcmil (one size thinner) at these inputs gives a voltage drop of 3.78V (3.15% on 120V), and its branch-circuit OCP cap under typical conditions is 255A.
Limiting factor here: voltage drop, not ampacity. 250 kcmil is still above the 183.33A load at its 255A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 3.15% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.
What If You Go One Size Larger?
Using 350 kcmil (one size thicker) would reduce voltage drop to 2.69V (2.24% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
183.33A at 120V delivers 21,999.6 watts (DC / resistive load). See conversion.