Wire Size for 25.47 Amps

Typical copper wire gauges for 25.47 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 25.47A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

25.47A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.58V (1.32%) check_circle OK
50 ft 10 AWG 3.16V (2.63%) check_circle OK
75 ft 8 AWG 2.97V (2.48%) check_circle OK
100 ft 6 AWG 2.5V (2.08%) check_circle OK
125 ft 6 AWG 3.13V (2.61%) check_circle OK
150 ft 4 AWG 2.35V (1.96%) check_circle OK
175 ft 4 AWG 2.75V (2.29%) check_circle OK
200 ft 4 AWG 3.14V (2.61%) check_circle OK
250 ft 3 AWG 3.12V (2.6%) check_circle OK
300 ft 2 AWG 2.96V (2.47%) check_circle OK
400 ft 1 AWG 3.14V (2.61%) check_circle OK
500 ft 1/0 AWG 3.11V (2.59%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.