What Wire Size for 25.47 Amps at 400 Feet?
1 AWG copper is a typical pick for 25.47A at 400 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 1 AWG at these inputs: 3.14V (2.61%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.
No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 400 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 25.47A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 1 AWG sits at a branch-circuit OCP of 130A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (1 AWG NM-B = 110A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 2 AWG (one size thinner) at these inputs gives a voltage drop of 3.95V (3.29% on 120V), and its branch-circuit OCP cap under typical conditions is 115A.
Limiting factor here: voltage drop, not ampacity. 2 AWG is still above the 25.47A load at its 115A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 3.29% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.
What If You Go One Size Larger?
Using 1/0 AWG (one size thicker) would reduce voltage drop to 2.49V (2.07% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
25.47A at 120V delivers 3,056.4 watts (DC / resistive load). See conversion.