What Wire Size for 289 Amps at 25 Feet?
350 kcmil copper is a typical pick for 289A at 25 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 350 kcmil at these inputs: 0.5303V (0.4419%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 289A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 350 kcmil sits at a branch-circuit OCP of 310A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (350 kcmil NM-B = 260A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 300 kcmil (one size thinner) at these inputs gives a voltage drop of 0.6199V (0.5166% on 120V), and its branch-circuit OCP cap under typical conditions is 285A.
Limiting factor here: branch-circuit ampacity. 300 kcmil has a branch-circuit OCP cap of 285A under the typical 75°C-termination assumptions used here, which is below the 289A load. For this load it shouldn't be used without reassessing against the actual termination temperature, cable type, ambient conditions, and any 240.4(D) or 240.4(B) provisions.
What If You Go One Size Larger?
Using 500 kcmil (one size thicker) would reduce voltage drop to 0.3728V (0.3107% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
289A at 120V delivers 34,680 watts (DC / resistive load). See conversion.