What Wire Size for 416.67 Amps at 75 Feet?
750 kcmil copper is a typical pick for 416.67A at 75 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 750 kcmil at these inputs: 1.07V (0.8906%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.
No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 75 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 416.67A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 750 kcmil sits at a branch-circuit OCP of 475A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (750 kcmil NM-B = 400A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 500 kcmil (one size thinner) at these inputs gives a voltage drop of 1.61V (1.34% on 120V), and its branch-circuit OCP cap under typical conditions is 380A.
Limiting factor here: branch-circuit ampacity. 500 kcmil has a branch-circuit OCP cap of 380A under the typical 75°C-termination assumptions used here, which is below the 416.67A load. For this load it shouldn't be used without reassessing against the actual termination temperature, cable type, ambient conditions, and any 240.4(D) or 240.4(B) provisions.
What If You Go One Size Larger?
The recommended gauge is already the largest available option.
Wattage at This Amperage
416.67A at 120V delivers 50,000.4 watts (DC / resistive load). See conversion.