What Wire Size for 44.23 Amps at 400 Feet?
For 44.23 amps at 400 feet on a 120V circuit, 2/0 AWG copper is a common starting point under a 3% voltage-drop target. On a 240V circuit the same current often allows 2 AWG, because the 3% allowable drop is a larger number of volts at higher source voltage. Actual install sizing still depends on conductor material, insulation/termination temperature, cable type, ambient and bundling conditions, and local code.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 44.23A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 2/0 AWG sits at a branch-circuit OCP of 175A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (2/0 AWG NM-B = 145A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 1/0 AWG (one size thinner) at these inputs gives a voltage drop of 4.32V (3.6% on 120V), and its branch-circuit OCP cap under typical conditions is 150A.
Limiting factor here: voltage drop, not ampacity. 1/0 AWG is still above the 44.23A load at its 150A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 3.6% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.
What If You Go One Size Larger?
Using 3/0 AWG (one size thicker) would reduce voltage drop to 2.71V (2.26% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
44.23A at 120V delivers 5,307.6 watts (DC / resistive load). See conversion.