How Many Amps Does a 0.25 HP three-phase Motor Draw at 240V?

At 240V, 0.25 horsepower equals roughly 0.621 amps per line of running current on a three-phase circuit. One HP is 746 watts of mechanical output, but motors are not 100% efficient, so the electrical draw is higher. Applying √3 × VL-L × Eff × PF: 186.5W ÷ (√3 × 240 × 0.85 × 0.85) = 186.5 ÷ 300.34 = 0.621 A.

Where you'll find 0.25 HP motors: small pool pumps, light-commercial fans, booster pumps.

0.25 HP three-phase motor at 240V
0.621 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLCoff-table (see nameplate)
Electrical input (HP × 746 ÷ efficiency)219.41 W
0.621
off-table

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(0.25 × 746) ÷ (√3 × 240 × 0.85 × 0.85) = 186.5 ÷ 300.34 = 0.621 A per line
  1. Convert HP to watts: 0.25 × 746 = 186.5W
  2. Denominator: √3 × 240 × 0.85 × 0.85 = 1.73 × 240 × 0.85 × 0.85 = 300.34
  3. Result: 186.5 ÷ 300.34 = 0.621 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

Off-Table: No Code-Anchored Sizing

This combination is off-table because 0.25 HP is not a listed horsepower rating in NEC Table 430.250. The table lists discrete HP values (for three-phase: 1/2, 3/4, 1, 1½, 2, 3, 5, 7½, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, and on up), and 0.25 HP falls between listed values. 240V itself is a standard three-phase voltage in the table.

Per NEC 430.6(A)(1) Exception, when a motor rating falls between listed HP values, the next higher listed HP is used for sizing. For 0.25 HP, that means looking at 0.5 HP in the table.

Because there is no table FLC to anchor the NEC 430.22 conductor and 430.52(C)(1) OCP math, this page deliberately does not show branch-circuit sizing values for this variant. Multiplying the 0.621 A calculated running current by 125% or 250% would produce numbers that look authoritative but are not what the code requires.

What to do instead:

  • Apply NEC 430.6(A)(1) Exception and size from the next higher listed HP: 0.5 HP three-phase at 240V. The table FLC shown on that page is the Code-authoritative number for your 0.25 HP branch circuit.
  • If this motor is actually single-phase, 0.25 HP single-phase at 240V is in NEC Table 430.248 with an FLC of 2.9 A.
  • Pull the motor nameplate FLC and have a licensed electrician apply the 430.22 (conductor) and 430.52(C)(1) (OCP) rules against that number. NEC 430.6(A)(1) Exception permits using the next-higher listed HP where the motor rating is between table values; your inspector may also accept nameplate-based sizing for unusual HP ratings.

Operating Cost

Motor mechanical output is 186.5 W (0.25 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 186.5 ÷ 0.85 = 219.41 W. At $0.17/kWh, running cost is $0.04/hour or $8.95/month at 8 hours/day. Full breakdown at 219.41 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 240V per line and PF 0.85:

EfficiencyAmps at 240V (per line)Watts ConsumedWaste Heat
75%0.7038 A248.67 W62.17 W
80%0.6598 A233.13 W46.63 W
85%0.621 A219.41 W32.91 W
90%0.5865 A207.22 W20.72 W
95%0.5556 A196.32 W9.82 W

Other HP Values at 240V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.3105 Aoff-tablen/a
1/6 HP0.4141 Aoff-tablen/a
1/4 HP0.621 Aoff-tablen/a
1/3 HP0.8279 Aoff-tablen/a
1/2 HP1.24 A2.2 A11-15.4 A
3/4 HP1.86 A3.2 A16-22.4 A
1 HP2.48 A4.2 A21-29.4 A
1.5 HP3.73 A6 A30-42 A
2 HP4.97 A6.8 A34-47.6 A
3 HP7.45 A9.6 A48-67.2 A
5 HP12.42 A15.2 A76-106.4 A
7.5 HP18.63 A22 A110-154 A
10 HP24.84 A28 A140-196 A
15 HP37.26 A42 A210-294 A
20 HP49.68 A54 A270-378 A
25 HP62.1 A68 A340-476 A
30 HP74.52 A80 A400-560 A
40 HP99.35 A104 A520-728 A
50 HP124.19 A130 A650-910 A
75 HP186.29 A192 A960-1,344 A

Frequently Asked Questions

At the terminals, a 0.25 HP three-phase motor at 240V draws about 0.621 amps per line at 85% efficiency and 0.85 power factor. This specific HP and voltage combination is outside NEC Table 430.250, so NEC branch-circuit sizing must come from the motor nameplate and a licensed electrician, not from the calculated value above.
NEC Table 430.52(C)(1) percentages apply to the table full-load current, and this combination is not listed in NEC Table 430.250. The input for the 430.52(C)(1) math here is the motor nameplate FLC, applied by a licensed electrician with the device-type percentage that matches the install (175% dual-element fuse, 250% inverse-time breaker, 300% non-time-delay fuse, 800% instantaneous-trip breaker).
Locked-rotor startup current is typically 5-7 times the NEC table full-load current. Because this HP/voltage combination is not listed in NEC Table 430.250, there is no code-authoritative starting number for the multiplier; refer to the motor nameplate NEMA code letter for the actual LRA value.
Motors typically run at PF 0.80-0.85 at full load. At no load, PF drops to 0.30-0.40. Low PF means the wire and breaker carry extra reactive current that does no useful mechanical work, which is why NEC motor sizing uses table FLC (which already accounts for typical PF) rather than a simple watts/volts calculation.
Operating cost is based on electrical input, not mechanical HP output. At 85% efficiency, a 0.25 HP motor draws about 219.41 W at the terminals. At $0.17/kWh (US residential average, last reviewed April 2026), that is $0.04/hour or $8.95/month at 8 hours/day.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.