How Many Amps Does a 7.5 HP three-phase Motor Draw at 240V?

A 7.5 HP three-phase motor at 240V draws approximately 18.63 amps per line during normal operation (85% efficiency, PF 0.85). Startup current can be 5-7 times the NEC Table 430.250 FLC (110-154 A) for a few seconds, which affects breaker and wire sizing.

7.5 HP three-phase motor at 240V
18.63 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLC (code sizing base)22 A
Conductor min ampacity (NEC 430.22, 125% of FLC)27.5 A
Electrical input (HP × 746 ÷ efficiency)6,582.35 W
18.63
22

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(7.5 × 746) ÷ (√3 × 240 × 0.85 × 0.85) = 5,595 ÷ 300.34 = 18.63 A per line
  1. Convert HP to watts: 7.5 × 746 = 5,595W
  2. Denominator: √3 × 240 × 0.85 × 0.85 = 1.73 × 240 × 0.85 × 0.85 = 300.34
  3. Result: 5,595 ÷ 300.34 = 18.63 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

NEC Sizing Base: NEC Table 430.250 FLC

Per NEC 430.6(A)(1), motor branch-circuit conductors, switches, and overcurrent protection are sized from the values in Table 430.248 (single-phase) or Table 430.250 (three-phase), not from the motor nameplate and not from a calculated full-load amps. For a 7.5 HP three-phase motor at 240V, the table value is 22 A (the 230V column covers 220-240V under 430.6(A)(1)).

The 18.63 A shown in the hero is the calculated running current at 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower under those assumptions, not a measured value; a real meter reading depends on the motor's actual efficiency, loading, temperature, and design. Use this figure for energy and metering estimates, and use 22 A as the reference FLC when an electrician walks through NEC 430 against the nameplate.

NEC 430.22 Conductor Rule (reference formula)

NEC 430.22 requires motor branch-circuit conductor ampacity of at least 125% of the Code sizing FLC. As a reference calculation against the NEC Table 430.250 value: 22 × 1.25 = 27.5 A. The selected conductor is taken from NEC Table 310.16 at the applicable termination temperature column, with ambient, bundling, and cable-type adjustments applied by the installer. Motor branch-circuit conductors are exempt from the 240.4(D) small-conductor rule via 240.4(G).

NEC 430.52 Overcurrent Protection (code caps)

NEC Table 430.52(C)(1) gives the maximum rating for motor short-circuit and ground-fault protection as a percentage of the Code sizing FLC. The percentage depends on the device type:

Device TypeMaximum % of Table FLC (430.52(C)(1))
Non-time-delay fuse300%
Dual-element (time-delay) fuse175%
Inverse-time circuit breaker250%
Instantaneous-trip circuit breaker800%

These percentages are maximum caps, not install picks. A real circuit applies the percentage against the Code sizing FLC for the specific device type, rounds up to a standard size per 430.52(C)(1)(a), and is verified against the motor nameplate and the install conditions by the installer. The elevated percentages exist so short-circuit protection does not nuisance-trip on locked-rotor startup inrush.

Locked Rotor (Startup) Current

During the first 2-5 seconds of startup, a squirrel-cage induction motor typically draws 5 to 7 times the NEC Table 430.250 FLC of 22 A (roughly 110 to 154 A). This is why the 430.52(C)(1) percentages above are so much higher than running current: the short-circuit/ground-fault protective device has to ride through locked-rotor inrush without tripping. Actual LRA is set by the motor's NEMA code letter on the nameplate and should be checked there for a real install.

CurrentAmpsDuration
Calculated running current (meter)18.63 A per lineContinuous at full load
NEC Table 430.250 FLC (Code reference)22 ASizing base, not metered
Locked rotor (typical, 5-7×)110-154 A2-5 seconds

Operating Cost

Motor mechanical output is 5,595 W (7.5 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 5,595 ÷ 0.85 = 6,582.35 W. At $0.17/kWh, running cost is $1.12/hour or $268.56/month at 8 hours/day. Full breakdown at 6,582.35 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 240V per line and PF 0.85:

EfficiencyAmps at 240V (per line)Watts ConsumedWaste Heat
75%21.11 A7,460 W1,865 W
80%19.79 A6,993.75 W1,398.75 W
85%18.63 A6,582.35 W987.35 W
90%17.59 A6,216.67 W621.67 W
95%16.67 A5,889.47 W294.47 W

Other HP Values at 240V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.3105 Aoff-tablen/a
1/6 HP0.4141 Aoff-tablen/a
1/4 HP0.621 Aoff-tablen/a
1/3 HP0.8279 Aoff-tablen/a
1/2 HP1.24 A2.2 A11-15.4 A
3/4 HP1.86 A3.2 A16-22.4 A
1 HP2.48 A4.2 A21-29.4 A
1.5 HP3.73 A6 A30-42 A
2 HP4.97 A6.8 A34-47.6 A
3 HP7.45 A9.6 A48-67.2 A
5 HP12.42 A15.2 A76-106.4 A
7.5 HP18.63 A22 A110-154 A
10 HP24.84 A28 A140-196 A
15 HP37.26 A42 A210-294 A
20 HP49.68 A54 A270-378 A
25 HP62.1 A68 A340-476 A
30 HP74.52 A80 A400-560 A
40 HP99.35 A104 A520-728 A
50 HP124.19 A130 A650-910 A
75 HP186.29 A192 A960-1,344 A

Frequently Asked Questions

At the terminals, a 7.5 HP three-phase motor at 240V draws about 18.63 amps per line at 85% efficiency and 0.85 power factor. For NEC branch-circuit sizing use the NEC Table 430.250 full-load current instead: 22 A.
Three-phase motor branches are not served from residential receptacles in the US. Three-phase power is distributed to commercial and industrial services, and a 7.5 HP three-phase motor at 240V needs a dedicated three-phase branch circuit sized by an electrician per NEC 430.22 (conductors) and 430.52(C)(1) (short-circuit / ground-fault protection), against the motor nameplate and install conditions.
NEC Table 430.52(C)(1) gives the maximum OCP rating as a percentage of the NEC Table 430.250 FLC. The ceilings by device type are 300% for non-time-delay fuses, 175% for dual-element (time-delay) fuses, 250% for inverse-time circuit breakers, and 800% for instantaneous-trip breakers. These percentages are ceilings, not starting points, and 250% is not a blanket motor rule. The actual max for a specific install comes from picking the device type, applying the matching percentage to the 22 A NEC Table 430.250 FLC, rounding up to a standard size per 430.52(C)(1)(a), and verifying against the motor startup profile.
NEC 430.22 requires motor branch-circuit conductors to have an ampacity of at least 125% of the NEC Table 430.250 FLC (not the motor nameplate, and not the calculated running current). As a reference formula against the table value: 22 A × 1.25. The specific conductor is picked from NEC Table 310.16 at the applicable termination temperature column, with ambient and bundling adjustments applied by the installer. Motor branches are exempt from the 240.4(D) small-conductor rule via 240.4(G).
Operating cost is based on electrical input, not mechanical HP output. At 85% efficiency, a 7.5 HP motor draws about 6,582.35 W at the terminals. At $0.17/kWh (US residential average, last reviewed April 2026), that is $1.12/hour or $268.56/month at 8 hours/day.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.