How Many Amps Does a 1.5 HP single-phase Motor Draw at 240V?

A 1.5 HP single-phase motor at 240V draws approximately 6.45 amps during normal operation (85% efficiency, PF 0.85). Startup current can be 5-7 times the NEC Table 430.248 FLC (50-70 A) for a few seconds, which affects breaker and wire sizing.

Common applications for 1.5 HP motors: air compressors, well pumps, woodworking tools, small shop equipment.

1.5 HP single-phase motor at 240V
6.45 Amps running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.248 FLC (code sizing base)10 A
Conductor min ampacity (NEC 430.22, 125% of FLC)12.5 A
Electrical input (HP × 746 ÷ efficiency)1,316.47 W
6.45
10

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (single-phase)

I(A) = (HP × 746) ÷ (V × Eff × PF)

(1.5 × 746) ÷ (240 × 0.85 × 0.85) = 1,119 ÷ 173.4 = 6.45 A
  1. Convert HP to watts: 1.5 × 746 = 1,119W
  2. Denominator: 240 × 0.85 × 0.85 = 173.4
  3. Result: 1,119 ÷ 173.4 = 6.45 amps

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

NEC Sizing Base: NEC Table 430.248 FLC

Per NEC 430.6(A)(1), motor branch-circuit conductors, switches, and overcurrent protection are sized from the values in Table 430.248 (single-phase) or Table 430.250 (three-phase), not from the motor nameplate and not from a calculated full-load amps. For a 1.5 HP single-phase motor at 240V, the table value is 10 A (the 115V column covers 110-120V systems under 430.6(A)(1)).

The 6.45 A shown in the hero is the calculated running current at 85% efficiency and PF 0.85. This is a conversion from the nameplate horsepower under those assumptions, not a measured value; a real meter reading depends on the motor's actual efficiency, loading, temperature, and design. Use this figure for energy and metering estimates, and use 10 A as the reference FLC when an electrician walks through NEC 430 against the nameplate.

NEC 430.22 Conductor Rule (reference formula)

NEC 430.22 requires motor branch-circuit conductor ampacity of at least 125% of the Code sizing FLC. As a reference calculation against the NEC Table 430.248 value: 10 × 1.25 = 12.5 A. The selected conductor is taken from NEC Table 310.16 at the applicable termination temperature column, with ambient, bundling, and cable-type adjustments applied by the installer. Motor branch-circuit conductors are exempt from the 240.4(D) small-conductor rule via 240.4(G).

NEC 430.52 Overcurrent Protection (code caps)

NEC Table 430.52(C)(1) gives the maximum rating for motor short-circuit and ground-fault protection as a percentage of the Code sizing FLC. The percentage depends on the device type:

Device TypeMaximum % of Table FLC (430.52(C)(1))
Non-time-delay fuse300%
Dual-element (time-delay) fuse175%
Inverse-time circuit breaker250%
Instantaneous-trip circuit breaker800%

These percentages are maximum caps, not install picks. A real circuit applies the percentage against the Code sizing FLC for the specific device type, rounds up to a standard size per 430.52(C)(1)(a), and is verified against the motor nameplate and the install conditions by the installer. The elevated percentages exist so short-circuit protection does not nuisance-trip on locked-rotor startup inrush.

Locked Rotor (Startup) Current

During the first 2-5 seconds of startup, a squirrel-cage induction motor typically draws 5 to 7 times the NEC Table 430.248 FLC of 10 A (roughly 50 to 70 A). This is why the 430.52(C)(1) percentages above are so much higher than running current: the short-circuit/ground-fault protective device has to ride through locked-rotor inrush without tripping. Actual LRA is set by the motor's NEMA code letter on the nameplate and should be checked there for a real install.

CurrentAmpsDuration
Calculated running current (meter)6.45 AContinuous at full load
NEC Table 430.248 FLC (Code reference)10 ASizing base, not metered
Locked rotor (typical, 5-7×)50-70 A2-5 seconds

Operating Cost

Motor mechanical output is 1,119 W (1.5 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 1,119 ÷ 0.85 = 1,316.47 W. At $0.17/kWh, running cost is $0.22/hour or $53.71/month at 8 hours/day. Full breakdown at 1,316.47 W.

Amps by Motor Efficiency (single-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated single-phase running current at 240V and PF 0.85:

EfficiencyAmps at 240VWatts ConsumedWaste Heat
75%7.31 A1,492 W373 W
80%6.86 A1,398.75 W279.75 W
85%6.45 A1,316.47 W197.47 W
90%6.09 A1,243.33 W124.33 W
95%5.77 A1,177.89 W58.89 W

Other HP Values at 240V (single-phase)

Running current is the calculated single-phase draw at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.248 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in single-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.248 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.5378 Aoff-tablen/a
1/6 HP0.7172 A2.2 A11-15.4 A
1/4 HP1.08 A2.9 A14.5-20.3 A
1/3 HP1.43 A3.6 A18-25.2 A
1/2 HP2.15 A4.9 A24.5-34.3 A
3/4 HP3.23 A6.9 A34.5-48.3 A
1 HP4.3 A8 A40-56 A
1.5 HP6.45 A10 A50-70 A
2 HP8.6 A12 A60-84 A
3 HP12.91 A17 A85-119 A
5 HP21.51 A28 A140-196 A
7.5 HP32.27 A40 A200-280 A
10 HP43.02 A50 A250-350 A
15 HP64.53 Aoff-tablen/a
20 HP86.04 Aoff-tablen/a
25 HP107.55 Aoff-tablen/a
30 HP129.07 Aoff-tablen/a
40 HP172.09 Aoff-tablen/a
50 HP215.11 Aoff-tablen/a
75 HP322.66 Aoff-tablen/a

Frequently Asked Questions

At the terminals, a 1.5 HP single-phase motor at 240V draws about 6.45 amps at 85% efficiency and 0.85 power factor. For NEC branch-circuit sizing use the NEC Table 430.248 full-load current instead: 10 A.
At 240V single-phase, motor branches are dedicated circuits, not general-purpose receptacles. Common NEMA configurations at this voltage are the 6-series (6-15, 6-20, 6-30, 6-50) and the 14-series (14-30, 14-50) when a neutral is needed, sized to the motor branch-circuit OCP the installer picks under NEC 430.52(C)(1). The NEC Table 430.248 FLC of 10 A is the reference number an electrician feeds into 430.22 and 430.52, not a receptacle pick on its own. Verify against the nameplate and local code.
Operating cost is based on electrical input, not mechanical HP output. At 85% efficiency, a 1.5 HP motor draws about 1,316.47 W at the terminals. At $0.17/kWh (US residential average, last reviewed April 2026), that is $0.22/hour or $53.71/month at 8 hours/day.
1.5 HP equals 1,119 watts of mechanical output (1 HP = 746 W). The electrical input at the terminals is higher because no motor is 100% efficient: at 85% efficiency the input is about 1,316.47 W.
Yes. A 1.5 HP single-phase motor at 90% efficiency draws 6.09 A at the terminals versus 7.31 A at 75% efficiency. Higher efficiency means lower running amps and lower electrical input wattage for the same mechanical output.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.