How Many Amps Does a 50 HP three-phase Motor Draw at 575V?

At 575V, 50 horsepower equals roughly 51.84 amps per line of running current on a three-phase circuit. One HP is 746 watts of mechanical output, but motors are not 100% efficient, so the electrical draw is higher. Applying √3 × VL-L × Eff × PF: 37,300W ÷ (√3 × 575 × 0.85 × 0.85) = 37,300 ÷ 719.56 = 51.84 A.

50 HP three-phase motor at 575V
51.84 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLC (code sizing base)52 A
Conductor min ampacity (NEC 430.22, 125% of FLC)65 A
Electrical input (HP × 746 ÷ efficiency)43,882.35 W
51.84
52

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(50 × 746) ÷ (√3 × 575 × 0.85 × 0.85) = 37,300 ÷ 719.56 = 51.84 A per line
  1. Convert HP to watts: 50 × 746 = 37,300W
  2. Denominator: √3 × 575 × 0.85 × 0.85 = 1.73 × 575 × 0.85 × 0.85 = 719.56
  3. Result: 37,300 ÷ 719.56 = 51.84 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

NEC Sizing Base: NEC Table 430.250 FLC

Per NEC 430.6(A)(1), motor branch-circuit conductors, switches, and overcurrent protection are sized from the values in Table 430.248 (single-phase) or Table 430.250 (three-phase), not from the motor nameplate and not from a calculated full-load amps. For a 50 HP three-phase motor at 575V, the table value is 52 A (the 460V column covers 440-480V under 430.6(A)(1)).

The 51.84 A shown in the hero is the calculated running current at 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower under those assumptions, not a measured value; a real meter reading depends on the motor's actual efficiency, loading, temperature, and design. Use this figure for energy and metering estimates, and use 52 A as the reference FLC when an electrician walks through NEC 430 against the nameplate.

NEC 430.22 Conductor Rule (reference formula)

NEC 430.22 requires motor branch-circuit conductor ampacity of at least 125% of the Code sizing FLC. As a reference calculation against the NEC Table 430.250 value: 52 × 1.25 = 65 A. The selected conductor is taken from NEC Table 310.16 at the applicable termination temperature column, with ambient, bundling, and cable-type adjustments applied by the installer. Motor branch-circuit conductors are exempt from the 240.4(D) small-conductor rule via 240.4(G).

NEC 430.52 Overcurrent Protection (code caps)

NEC Table 430.52(C)(1) gives the maximum rating for motor short-circuit and ground-fault protection as a percentage of the Code sizing FLC. The percentage depends on the device type:

Device TypeMaximum % of Table FLC (430.52(C)(1))
Non-time-delay fuse300%
Dual-element (time-delay) fuse175%
Inverse-time circuit breaker250%
Instantaneous-trip circuit breaker800%

These percentages are maximum caps, not install picks. A real circuit applies the percentage against the Code sizing FLC for the specific device type, rounds up to a standard size per 430.52(C)(1)(a), and is verified against the motor nameplate and the install conditions by the installer. The elevated percentages exist so short-circuit protection does not nuisance-trip on locked-rotor startup inrush.

Locked Rotor (Startup) Current

During the first 2-5 seconds of startup, a squirrel-cage induction motor typically draws 5 to 7 times the NEC Table 430.250 FLC of 52 A (roughly 260 to 364 A). This is why the 430.52(C)(1) percentages above are so much higher than running current: the short-circuit/ground-fault protective device has to ride through locked-rotor inrush without tripping. Actual LRA is set by the motor's NEMA code letter on the nameplate and should be checked there for a real install.

CurrentAmpsDuration
Calculated running current (meter)51.84 A per lineContinuous at full load
NEC Table 430.250 FLC (Code reference)52 ASizing base, not metered
Locked rotor (typical, 5-7×)260-364 A2-5 seconds

Operating Cost

Motor mechanical output is 37,300 W (50 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 37,300 ÷ 0.85 = 43,882.35 W. At $0.17/kWh, running cost is $7.46/hour or $1,790.40/month at 8 hours/day. Full breakdown at 43,882.35 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 575V per line and PF 0.85:

EfficiencyAmps at 575V (per line)Watts ConsumedWaste Heat
75%58.75 A49,733.33 W12,433.33 W
80%55.08 A46,625 W9,325 W
85%51.84 A43,882.35 W6,582.35 W
90%48.96 A41,444.44 W4,144.44 W
95%46.38 A39,263.16 W1,963.16 W

Other HP Values at 575V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.1296 Aoff-tablen/a
1/6 HP0.1728 Aoff-tablen/a
1/4 HP0.2592 Aoff-tablen/a
1/3 HP0.3455 Aoff-tablen/a
1/2 HP0.5184 A0.9 A4.5-6.3 A
3/4 HP0.7776 A1.3 A6.5-9.1 A
1 HP1.04 A1.7 A8.5-11.9 A
1.5 HP1.56 A2.4 A12-16.8 A
2 HP2.07 A2.7 A13.5-18.9 A
3 HP3.11 A3.9 A19.5-27.3 A
5 HP5.18 A6.1 A30.5-42.7 A
7.5 HP7.78 A9 A45-63 A
10 HP10.37 A11 A55-77 A
15 HP15.55 A17 A85-119 A
20 HP20.73 A22 A110-154 A
25 HP25.92 A27 A135-189 A
30 HP31.1 A32 A160-224 A
40 HP41.47 A41 A205-287 A
50 HP51.84 A52 A260-364 A
75 HP77.76 A77 A385-539 A

Frequently Asked Questions

At the terminals, a 50 HP three-phase motor at 575V draws about 51.84 amps per line at 85% efficiency and 0.85 power factor. For NEC branch-circuit sizing use the NEC Table 430.250 full-load current instead: 52 A.
Yes. A 50 HP three-phase motor at 90% efficiency draws 48.96 A at the terminals versus 58.75 A at 75% efficiency. Higher efficiency means lower running amps and lower electrical input wattage for the same mechanical output.
50 HP equals 37,300 watts of mechanical output (1 HP = 746 W). The electrical input at the terminals is higher because no motor is 100% efficient: at 85% efficiency the input is about 43,882.35 W.
NEC Table 430.52(C)(1) gives the maximum OCP rating as a percentage of the NEC Table 430.250 FLC. The ceilings by device type are 300% for non-time-delay fuses, 175% for dual-element (time-delay) fuses, 250% for inverse-time circuit breakers, and 800% for instantaneous-trip breakers. These percentages are ceilings, not starting points, and 250% is not a blanket motor rule. The actual max for a specific install comes from picking the device type, applying the matching percentage to the 52 A NEC Table 430.250 FLC, rounding up to a standard size per 430.52(C)(1)(a), and verifying against the motor startup profile.
Operating cost is based on electrical input, not mechanical HP output. At 85% efficiency, a 50 HP motor draws about 43,882.35 W at the terminals. At $0.17/kWh (US residential average, last reviewed April 2026), that is $7.46/hour or $1,790.40/month at 8 hours/day.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.