How Many Amps Does a 50 HP three-phase Motor Draw at 400V?

A 50 HP three-phase motor at 400V draws approximately 74.52 amps per line during normal operation (85% efficiency, PF 0.85). This HP and voltage combination is outside NEC Table 430.250, so there is no code-authoritative LRA multiplier for branch-circuit sizing; refer to the motor nameplate for both running current and startup characteristics.

50 HP three-phase motor at 400V
74.52 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLCoff-table (see nameplate)
Electrical input (HP × 746 ÷ efficiency)43,882.35 W
74.52
off-table

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(50 × 746) ÷ (√3 × 400 × 0.85 × 0.85) = 37,300 ÷ 500.56 = 74.52 A per line
  1. Convert HP to watts: 50 × 746 = 37,300W
  2. Denominator: √3 × 400 × 0.85 × 0.85 = 1.73 × 400 × 0.85 × 0.85 = 500.56
  3. Result: 37,300 ÷ 500.56 = 74.52 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

Off-Table: No Code-Anchored Sizing

This combination is off-table because 400V is not a listed three-phase voltage in NEC Table 430.250. The table lists three-phase motors at 200V, 208V, 230V, 460V, and 575V, three-phase power is not typically distributed at 120V, 240V single-leg, 277V, or 400V in the United States. 50 HP is a listed horsepower, but not at this voltage.

Because there is no table FLC to anchor the NEC 430.22 conductor and 430.52(C)(1) OCP math, this page deliberately does not show branch-circuit sizing values for this variant. Multiplying the 74.52 A calculated running current by 125% or 250% would produce numbers that look authoritative but are not what the code requires.

What to do instead:

  • Use one of the voltages NEC Table 430.250 actually lists for 50 HP three-phase: 50 HP at 208V 3Φ, 50 HP at 230V 3Φ, 50 HP at 480V 3Φ, 50 HP at 575V 3Φ.
  • Pull the motor nameplate FLC and have a licensed electrician apply the 430.22 (conductor) and 430.52(C)(1) (OCP) rules against that number. NEC 430.6(A)(1) Exception permits using the next-higher listed HP where the motor rating is between table values; your inspector may also accept nameplate-based sizing for unusual HP ratings.

Operating Cost

Motor mechanical output is 37,300 W (50 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 37,300 ÷ 0.85 = 43,882.35 W. At $0.17/kWh, running cost is $7.46/hour or $1,790.40/month at 8 hours/day. Full breakdown at 43,882.35 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 400V per line and PF 0.85:

EfficiencyAmps at 400V (per line)Watts ConsumedWaste Heat
75%84.45 A49,733.33 W12,433.33 W
80%79.17 A46,625 W9,325 W
85%74.52 A43,882.35 W6,582.35 W
90%70.38 A41,444.44 W4,144.44 W
95%66.67 A39,263.16 W1,963.16 W

Other HP Values at 400V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.1863 Aoff-tablen/a
1/6 HP0.2484 Aoff-tablen/a
1/4 HP0.3726 Aoff-tablen/a
1/3 HP0.4967 Aoff-tablen/a
1/2 HP0.7452 Aoff-tablen/a
3/4 HP1.12 Aoff-tablen/a
1 HP1.49 Aoff-tablen/a
1.5 HP2.24 Aoff-tablen/a
2 HP2.98 Aoff-tablen/a
3 HP4.47 Aoff-tablen/a
5 HP7.45 Aoff-tablen/a
7.5 HP11.18 Aoff-tablen/a
10 HP14.9 Aoff-tablen/a
15 HP22.35 Aoff-tablen/a
20 HP29.81 Aoff-tablen/a
25 HP37.26 Aoff-tablen/a
30 HP44.71 Aoff-tablen/a
40 HP59.61 Aoff-tablen/a
50 HP74.52 Aoff-tablen/a
75 HP111.77 Aoff-tablen/a

Frequently Asked Questions

At the terminals, a 50 HP three-phase motor at 400V draws about 74.52 amps per line at 85% efficiency and 0.85 power factor. This specific HP and voltage combination is outside NEC Table 430.250, so NEC branch-circuit sizing must come from the motor nameplate and a licensed electrician, not from the calculated value above.
Three-phase motor branches are not served from residential receptacles in the US. Three-phase power is distributed to commercial and industrial services, and a 50 HP three-phase motor at 400V needs a dedicated three-phase branch circuit sized by an electrician per NEC 430.22 (conductors) and 430.52(C)(1) (short-circuit / ground-fault protection), against the motor nameplate and install conditions.
Locked-rotor startup current is typically 5-7 times the NEC table full-load current. Because this HP/voltage combination is not listed in NEC Table 430.250, there is no code-authoritative starting number for the multiplier; refer to the motor nameplate NEMA code letter for the actual LRA value.
50 HP equals 37,300 watts of mechanical output (1 HP = 746 W). The electrical input at the terminals is higher because no motor is 100% efficient: at 85% efficiency the input is about 43,882.35 W.
NEC 430.22 sizes branch-circuit conductors at 125% of the table full-load current, but this HP/voltage combination is not listed in NEC Table 430.250. The correct input for the 430.22 formula here is the motor nameplate FLC, applied by a licensed electrician.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.