What Is the Voltage Drop for 1/0 AWG at 26A and 500 Feet?

Running 26A through 1/0 AWG copper for 500 feet on a single-phase / DC circuit produces a 3.17-volt drop. On a 120V source that is 2.64%; on 240V it is 1.32%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 26A, 500ft · single-phase / DC
3.17 V drop (2.64% on 120V)
On 120V circuit2.64%
On 240V circuit1.32%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
3.17V (2.64%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 26 × 0.122) ÷ 1000 = 3.17 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.17 ÷ 120) × 100 = 2.64%
On 240V: (3.17 ÷ 240) × 100 = 1.32%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 26A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1586V0.1322%0.0661%OK
50ft0.3172V0.2643%0.1322%OK
75ft0.4758V0.3965%0.1982%OK
100ft0.6344V0.5287%0.2643%OK
150ft0.9516V0.793%0.3965%OK
200ft1.27V1.06%0.5287%OK
300ft1.9V1.59%0.793%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 26A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 26A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG3.17V2.64%1.32%OK
2/0 AWG2.51V2.1%1.05%OK
3/0 AWG1.99V1.66%0.8298%OK
4/0 AWG1.58V1.32%0.6587%OK
250 kcmil1.34V1.12%0.5579%OK
300 kcmil1.12V0.9295%0.4648%OK

Frequently Asked Questions

1/0 AWG carrying 26A over 500ft has a 3.17V drop (2.64% on 120V). Reference: 1.32% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.64% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 2.64%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.