What Is the Voltage Drop for 2/0 AWG at 113A and 175 Feet?

2/0 AWG copper carrying 113 amps over 175 feet on a single-phase / DC circuit drops 3.82 volts (3.19% on a 120V source). This sits past the 3% target NEC 210.19(A) Informational Note 4 cites for branch circuits, but within the 5% target for feeder+branch total. Which one applies depends on whether this run is a branch circuit, a feeder, or a feeder+branch combined: if it's a branch circuit, it's past target; if it's a feeder alone or part of a feeder+branch combined system, the 5% total is the figure to check against whatever the upstream drop adds. Both are planning targets, not code requirements.

2/0 AWG, 113A, 175ft · single-phase / DC
3.82 V drop (3.19% on 120V)
On 120V circuit3.19%
On 240V circuit1.59%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
3.82V (3.19%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 113 × 0.0967) ÷ 1000 = 3.82 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.82 ÷ 120) × 100 = 3.19%
On 240V: (3.82 ÷ 240) × 100 = 1.59%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 113A over 175ft on 120V is 3/0 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 113A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5464V0.4553%0.2276%OK
50ft1.09V0.9106%0.4553%OK
75ft1.64V1.37%0.6829%OK
100ft2.19V1.82%0.9106%OK
150ft3.28V2.73%1.37%OK
200ft4.37V3.64%1.82%Caution
300ft6.56V5.46%2.73%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 113A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 113A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG3.82V3.19%1.59%Caution
3/0 AWG3.03V2.52%1.26%OK
4/0 AWG2.4V2%1%OK
250 kcmil2.04V1.7%0.8487%OK
300 kcmil1.7V1.41%0.707%OK
350 kcmil1.45V1.21%0.6048%OK

Frequently Asked Questions

2/0 AWG carrying 113A over 175ft has a 3.82V drop (3.19% on 120V). Reference: 1.59% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 3.19%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.59% on 240V versus 3.19% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.