What Is the Voltage Drop for 2/0 AWG at 116A and 25 Feet?

2/0 AWG copper carrying 116 amps over 25 feet on a single-phase / DC circuit drops 0.5609 volts (0.4674% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 116A, 25ft · single-phase / DC
0.5609 V drop (0.4674% on 120V)
On 120V circuit0.4674%
On 240V circuit0.2337%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.56V (0.47%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 116 × 0.0967) ÷ 1000 = 0.5609 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5609 ÷ 120) × 100 = 0.4674%
On 240V: (0.5609 ÷ 240) × 100 = 0.2337%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 116A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5609V0.4674%0.2337%OK
50ft1.12V0.9348%0.4674%OK
75ft1.68V1.4%0.7011%OK
100ft2.24V1.87%0.9348%OK
150ft3.37V2.8%1.4%OK
200ft4.49V3.74%1.87%Caution
300ft6.73V5.61%2.8%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 116A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 116A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.5609V0.4674%0.2337%OK
3/0 AWG0.4443V0.3702%0.1851%OK
4/0 AWG0.3526V0.2939%0.1469%OK
250 kcmil0.2987V0.2489%0.1245%OK
300 kcmil0.2488V0.2073%0.1037%OK
350 kcmil0.2129V0.1774%0.0887%OK

Frequently Asked Questions

2/0 AWG carrying 116A over 25ft has a 0.5609V drop (0.4674% on 120V). Reference: 0.2337% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.4674%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2337% on 240V versus 0.4674% on 120V.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4674% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.