What Is the Voltage Drop for 2/0 AWG at 118A and 25 Feet?

2/0 AWG at 118A and 25 feet: 0.5705V drop (0.4754% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2/0 AWG, 118A, 25ft · single-phase / DC
0.5705 V drop (0.4754% on 120V)
On 120V circuit0.4754%
On 240V circuit0.2377%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.57V (0.48%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 118 × 0.0967) ÷ 1000 = 0.5705 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5705 ÷ 120) × 100 = 0.4754%
On 240V: (0.5705 ÷ 240) × 100 = 0.2377%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 118A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5705V0.4754%0.2377%OK
50ft1.14V0.9509%0.4754%OK
75ft1.71V1.43%0.7132%OK
100ft2.28V1.9%0.9509%OK
150ft3.42V2.85%1.43%OK
200ft4.56V3.8%1.9%Caution
300ft6.85V5.71%2.85%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 118A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 118A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.5705V0.4754%0.2377%OK
3/0 AWG0.4519V0.3766%0.1883%OK
4/0 AWG0.3587V0.2989%0.1495%OK
250 kcmil0.3038V0.2532%0.1266%OK
300 kcmil0.2531V0.2109%0.1055%OK
350 kcmil0.2165V0.1804%0.0902%OK

Frequently Asked Questions

2/0 AWG carrying 118A over 25ft has a 0.5705V drop (0.4754% on 120V). Reference: 0.2377% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2377% on 240V versus 0.4754% on 120V.
On 120V, this run sits at 0.4754%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4754% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.