What Is the Voltage Drop for 2/0 AWG at 11A and 25 Feet?

2/0 AWG copper carrying 11 amps over 25 feet on a single-phase / DC circuit drops 0.0532 volts (0.0443% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 11A, 25ft · single-phase / DC
0.0532 V drop (0.0443% on 120V)
On 120V circuit0.0443%
On 240V circuit0.0222%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.05V (0.04%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 11 × 0.0967) ÷ 1000 = 0.0532 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.0532 ÷ 120) × 100 = 0.0443%
On 240V: (0.0532 ÷ 240) × 100 = 0.0222%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 11A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0532V0.0443%0.0222%OK
50ft0.1064V0.0886%0.0443%OK
75ft0.1596V0.133%0.0665%OK
100ft0.2127V0.1773%0.0886%OK
150ft0.3191V0.2659%0.133%OK
200ft0.4255V0.3546%0.1773%OK
300ft0.6382V0.5318%0.2659%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 11A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 11A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.0532V0.0443%0.0222%OK
3/0 AWG0.0421V0.0351%0.0176%OK
4/0 AWG0.0334V0.0279%0.0139%OK
250 kcmil0.0283V0.0236%0.0118%OK
300 kcmil0.0236V0.0197%0.009831%OK
350 kcmil0.0202V0.0168%0.00841%OK

Frequently Asked Questions

2/0 AWG carrying 11A over 25ft has a 0.0532V drop (0.0443% on 120V). Reference: 0.0222% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.0443%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.0443% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.0222% on 240V versus 0.0443% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.