What Is the Voltage Drop for 2/0 AWG at 167A and 100 Feet?

2/0 AWG copper carrying 167 amps over 100 feet on a single-phase / DC circuit drops 3.23 volts (2.69% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 167A, 100ft · single-phase / DC
3.23 V drop (2.69% on 120V)
On 120V circuit2.69%
On 240V circuit1.35%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
3.23V (2.69%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 167 × 0.0967) ÷ 1000 = 3.23 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.23 ÷ 120) × 100 = 2.69%
On 240V: (3.23 ÷ 240) × 100 = 1.35%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 167A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.8074V0.6729%0.3364%OK
50ft1.61V1.35%0.6729%OK
75ft2.42V2.02%1.01%OK
100ft3.23V2.69%1.35%OK
150ft4.84V4.04%2.02%Caution
200ft6.46V5.38%2.69%Past 5%
300ft9.69V8.07%4.04%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 167A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 167A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG3.23V2.69%1.35%OK
3/0 AWG2.56V2.13%1.07%OK
4/0 AWG2.03V1.69%0.8461%OK
250 kcmil1.72V1.43%0.7167%OK
300 kcmil1.43V1.19%0.597%OK
350 kcmil1.23V1.02%0.5107%OK

Frequently Asked Questions

2/0 AWG carrying 167A over 100ft has a 3.23V drop (2.69% on 120V). Reference: 1.35% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.69%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.35% on 240V versus 2.69% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.