What Is the Voltage Drop for 2/0 AWG at 17A and 250 Feet?

2/0 AWG copper carrying 17 amps over 250 feet on a single-phase / DC circuit drops 0.822 volts (0.685% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 17A, 250ft · single-phase / DC
0.822 V drop (0.685% on 120V)
On 120V circuit0.685%
On 240V circuit0.3425%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.82V (0.68%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 17 × 0.0967) ÷ 1000 = 0.822 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.822 ÷ 120) × 100 = 0.685%
On 240V: (0.822 ÷ 240) × 100 = 0.3425%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 17A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0822V0.0685%0.0342%OK
50ft0.1644V0.137%0.0685%OK
75ft0.2466V0.2055%0.1027%OK
100ft0.3288V0.274%0.137%OK
150ft0.4932V0.411%0.2055%OK
200ft0.6576V0.548%0.274%OK
300ft0.9863V0.822%0.411%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 17A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 17A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.822V0.685%0.3425%OK
3/0 AWG0.6511V0.5426%0.2713%OK
4/0 AWG0.5168V0.4307%0.2153%OK
250 kcmil0.4378V0.3648%0.1824%OK
300 kcmil0.3647V0.3039%0.1519%OK
350 kcmil0.312V0.26%0.13%OK

Frequently Asked Questions

2/0 AWG carrying 17A over 250ft has a 0.822V drop (0.685% on 120V). Reference: 0.3425% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.685%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3425% on 240V versus 0.685% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.