What Is the Voltage Drop for 2/0 AWG at 35A and 125 Feet?

Running 35A through 2/0 AWG copper for 125 feet on a single-phase / DC circuit produces a 0.8461-volt drop. On a 120V source that is 0.7051%; on 240V it is 0.3526%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2/0 AWG, 35A, 125ft · single-phase / DC
0.8461 V drop (0.7051% on 120V)
On 120V circuit0.7051%
On 240V circuit0.3526%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.85V (0.71%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 35 × 0.0967) ÷ 1000 = 0.8461 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.8461 ÷ 120) × 100 = 0.7051%
On 240V: (0.8461 ÷ 240) × 100 = 0.3526%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 35A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1692V0.141%0.0705%OK
50ft0.3385V0.282%0.141%OK
75ft0.5077V0.4231%0.2115%OK
100ft0.6769V0.5641%0.282%OK
150ft1.02V0.8461%0.4231%OK
200ft1.35V1.13%0.5641%OK
300ft2.03V1.69%0.8461%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 35A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 35A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.8461V0.7051%0.3526%OK
3/0 AWG0.6703V0.5585%0.2793%OK
4/0 AWG0.532V0.4433%0.2217%OK
250 kcmil0.4506V0.3755%0.1878%OK
300 kcmil0.3754V0.3128%0.1564%OK
350 kcmil0.3211V0.2676%0.1338%OK

Frequently Asked Questions

2/0 AWG carrying 35A over 125ft has a 0.8461V drop (0.7051% on 120V). Reference: 0.3526% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.7051%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3526% on 240V versus 0.7051% on 120V.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7051% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.