What Is the Voltage Drop for 2/0 AWG at 35A and 250 Feet?

2/0 AWG copper carrying 35 amps over 250 feet on a single-phase / DC circuit drops 1.69 volts (1.41% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 35A, 250ft · single-phase / DC
1.69 V drop (1.41% on 120V)
On 120V circuit1.41%
On 240V circuit0.7051%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
1.69V (1.41%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 35 × 0.0967) ÷ 1000 = 1.69 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.69 ÷ 120) × 100 = 1.41%
On 240V: (1.69 ÷ 240) × 100 = 0.7051%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 35A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1692V0.141%0.0705%OK
50ft0.3385V0.282%0.141%OK
75ft0.5077V0.4231%0.2115%OK
100ft0.6769V0.5641%0.282%OK
150ft1.02V0.8461%0.4231%OK
200ft1.35V1.13%0.5641%OK
300ft2.03V1.69%0.8461%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 35A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 35A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG1.69V1.41%0.7051%OK
3/0 AWG1.34V1.12%0.5585%OK
4/0 AWG1.06V0.8867%0.4433%OK
250 kcmil0.9013V0.751%0.3755%OK
300 kcmil0.7508V0.6256%0.3128%OK
350 kcmil0.6423V0.5352%0.2676%OK

Frequently Asked Questions

2/0 AWG carrying 35A over 250ft has a 1.69V drop (1.41% on 120V). Reference: 0.7051% on 240V.
On 120V, this run sits at 1.41%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7051% on 240V versus 1.41% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.