What Is the Voltage Drop for 2/0 AWG at 36A and 50 Feet?

2/0 AWG at 36A and 50 feet: 0.3481V drop (0.2901% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2/0 AWG, 36A, 50ft · single-phase / DC
0.3481 V drop (0.2901% on 120V)
On 120V circuit0.2901%
On 240V circuit0.145%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.35V (0.29%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 36 × 0.0967) ÷ 1000 = 0.3481 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.3481 ÷ 120) × 100 = 0.2901%
On 240V: (0.3481 ÷ 240) × 100 = 0.145%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 36A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1741V0.145%0.0725%OK
50ft0.3481V0.2901%0.145%OK
75ft0.5222V0.4351%0.2176%OK
100ft0.6962V0.5802%0.2901%OK
150ft1.04V0.8703%0.4351%OK
200ft1.39V1.16%0.5802%OK
300ft2.09V1.74%0.8703%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 36A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 36A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.3481V0.2901%0.145%OK
3/0 AWG0.2758V0.2298%0.1149%OK
4/0 AWG0.2189V0.1824%0.0912%OK
250 kcmil0.1854V0.1545%0.0773%OK
300 kcmil0.1544V0.1287%0.0643%OK
350 kcmil0.1321V0.1101%0.0551%OK

Frequently Asked Questions

2/0 AWG carrying 36A over 50ft has a 0.3481V drop (0.2901% on 120V). Reference: 0.145% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.2901% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.2901%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.