What Is the Voltage Drop for 2/0 AWG at 39A and 200 Feet?

2/0 AWG at 39A and 200 feet: 1.51V drop (1.26% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2/0 AWG, 39A, 200ft · single-phase / DC
1.51 V drop (1.26% on 120V)
On 120V circuit1.26%
On 240V circuit0.6286%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
1.51V (1.26%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 39 × 0.0967) ÷ 1000 = 1.51 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.51 ÷ 120) × 100 = 1.26%
On 240V: (1.51 ÷ 240) × 100 = 0.6286%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 39A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1886V0.1571%0.0786%OK
50ft0.3771V0.3143%0.1571%OK
75ft0.5657V0.4714%0.2357%OK
100ft0.7543V0.6286%0.3143%OK
150ft1.13V0.9428%0.4714%OK
200ft1.51V1.26%0.6286%OK
300ft2.26V1.89%0.9428%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 39A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 39A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG1.51V1.26%0.6286%OK
3/0 AWG1.19V0.9958%0.4979%OK
4/0 AWG0.9485V0.7904%0.3952%OK
250 kcmil0.8034V0.6695%0.3348%OK
300 kcmil0.6692V0.5577%0.2789%OK
350 kcmil0.5725V0.4771%0.2386%OK

Frequently Asked Questions

2/0 AWG carrying 39A over 200ft has a 1.51V drop (1.26% on 120V). Reference: 0.6286% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.26% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.26%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.