What Is the Voltage Drop for 2/0 AWG at 49A and 75 Feet?

Running 49A through 2/0 AWG copper for 75 feet on a single-phase / DC circuit produces a 0.7107-volt drop. On a 120V source that is 0.5923%; on 240V it is 0.2961%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2/0 AWG, 49A, 75ft · single-phase / DC
0.7107 V drop (0.5923% on 120V)
On 120V circuit0.5923%
On 240V circuit0.2961%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
0.71V (0.59%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 49 × 0.0967) ÷ 1000 = 0.7107 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.7107 ÷ 120) × 100 = 0.5923%
On 240V: (0.7107 ÷ 240) × 100 = 0.2961%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 49A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2369V0.1974%0.0987%OK
50ft0.4738V0.3949%0.1974%OK
75ft0.7107V0.5923%0.2961%OK
100ft0.9477V0.7897%0.3949%OK
150ft1.42V1.18%0.5923%OK
200ft1.9V1.58%0.7897%OK
300ft2.84V2.37%1.18%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 49A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 49A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG0.7107V0.5923%0.2961%OK
3/0 AWG0.563V0.4692%0.2346%OK
4/0 AWG0.4469V0.3724%0.1862%OK
250 kcmil0.3785V0.3154%0.1577%OK
300 kcmil0.3153V0.2628%0.1314%OK
350 kcmil0.2697V0.2248%0.1124%OK

Frequently Asked Questions

2/0 AWG carrying 49A over 75ft has a 0.7107V drop (0.5923% on 120V). Reference: 0.2961% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.5923%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.5923% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2961% on 240V versus 0.5923% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.