What Is the Voltage Drop for 2/0 AWG at 60A and 175 Feet?

Running 60A through 2/0 AWG copper for 175 feet on a single-phase / DC circuit produces a 2.03-volt drop. On a 120V source that is 1.69%; on 240V it is 0.8461%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2/0 AWG, 60A, 175ft · single-phase / DC
2.03 V drop (1.69% on 120V)
On 120V circuit1.69%
On 240V circuit0.8461%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
2.03V (1.69%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 60 × 0.0967) ÷ 1000 = 2.03 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.03 ÷ 120) × 100 = 1.69%
On 240V: (2.03 ÷ 240) × 100 = 0.8461%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 60A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2901V0.2418%0.1209%OK
50ft0.5802V0.4835%0.2418%OK
75ft0.8703V0.7253%0.3626%OK
100ft1.16V0.967%0.4835%OK
150ft1.74V1.45%0.7253%OK
200ft2.32V1.93%0.967%OK
300ft3.48V2.9%1.45%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 60A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 60A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG2.03V1.69%0.8461%OK
3/0 AWG1.61V1.34%0.6703%OK
4/0 AWG1.28V1.06%0.532%OK
250 kcmil1.08V0.9013%0.4506%OK
300 kcmil0.9009V0.7507%0.3754%OK
350 kcmil0.7707V0.6423%0.3211%OK

Frequently Asked Questions

2/0 AWG carrying 60A over 175ft has a 2.03V drop (1.69% on 120V). Reference: 0.8461% on 240V.
On 120V, this run sits at 1.69%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.8461% on 240V versus 1.69% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.69% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.