What Is the Voltage Drop for 2/0 AWG at 81A and 75 Feet?

2/0 AWG copper carrying 81 amps over 75 feet on a single-phase / DC circuit drops 1.17 volts (0.9791% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2/0 AWG, 81A, 75ft · single-phase / DC
1.17 V drop (0.9791% on 120V)
On 120V circuit0.9791%
On 240V circuit0.4895%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2/0 AWG
1.17V (0.98%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 81 × 0.0967) ÷ 1000 = 1.17 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.17 ÷ 120) × 100 = 0.9791%
On 240V: (1.17 ÷ 240) × 100 = 0.4895%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2/0 AWG at 81A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3916V0.3264%0.1632%OK
50ft0.7833V0.6527%0.3264%OK
75ft1.17V0.9791%0.4895%OK
100ft1.57V1.31%0.6527%OK
150ft2.35V1.96%0.9791%OK
200ft3.13V2.61%1.31%OK
300ft4.7V3.92%1.96%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 81A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 81A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2/0 AWG1.17V0.9791%0.4895%OK
3/0 AWG0.9307V0.7756%0.3878%OK
4/0 AWG0.7387V0.6156%0.3078%OK
250 kcmil0.6257V0.5214%0.2607%OK
300 kcmil0.5212V0.4344%0.2172%OK
350 kcmil0.4459V0.3716%0.1858%OK

Frequently Asked Questions

2/0 AWG carrying 81A over 75ft has a 1.17V drop (0.9791% on 120V). Reference: 0.4895% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.4895% on 240V versus 0.9791% on 120V.
2/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.9791% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.9791%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.