What Is the Voltage Drop for 2 AWG at 35A and 250 Feet?

2 AWG copper carrying 35 amps over 250 feet on a single-phase / DC circuit drops 3.4 volts (2.83% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2 AWG, 35A, 250ft · single-phase / DC
3.4 V drop (2.83% on 120V)
On 120V circuit2.83%
On 240V circuit1.41%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
3.40V (2.83%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 35 × 0.194) ÷ 1000 = 3.4 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.4 ÷ 120) × 100 = 2.83%
On 240V: (3.4 ÷ 240) × 100 = 1.41%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 35A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3395V0.2829%0.1415%OK
50ft0.679V0.5658%0.2829%OK
75ft1.02V0.8488%0.4244%OK
100ft1.36V1.13%0.5658%OK
150ft2.04V1.7%0.8488%OK
200ft2.72V2.26%1.13%OK
300ft4.07V3.4%1.7%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 35A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 35A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG3.4V2.83%1.41%OK
1 AWG2.7V2.25%1.12%OK
1/0 AWG2.14V1.78%0.8896%OK
2/0 AWG1.69V1.41%0.7051%OK
3/0 AWG1.34V1.12%0.5585%OK
4/0 AWG1.06V0.8867%0.4433%OK

Frequently Asked Questions

2 AWG carrying 35A over 250ft has a 3.4V drop (2.83% on 120V). Reference: 1.41% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.83%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.41% on 240V versus 2.83% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.