What Is the Voltage Drop for 3/0 AWG at 25A and 500 Feet?

3/0 AWG copper carrying 25 amps over 500 feet on a single-phase / DC circuit drops 1.92 volts (1.6% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3/0 AWG, 25A, 500ft · single-phase / DC
1.92 V drop (1.6% on 120V)
On 120V circuit1.6%
On 240V circuit0.7979%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
1.92V (1.60%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 25 × 0.0766) ÷ 1000 = 1.92 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.92 ÷ 120) × 100 = 1.6%
On 240V: (1.92 ÷ 240) × 100 = 0.7979%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 25A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0958V0.0798%0.0399%OK
50ft0.1915V0.1596%0.0798%OK
75ft0.2873V0.2394%0.1197%OK
100ft0.383V0.3192%0.1596%OK
150ft0.5745V0.4788%0.2394%OK
200ft0.766V0.6383%0.3192%OK
300ft1.15V0.9575%0.4788%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 25A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 25A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG1.92V1.6%0.7979%OK
4/0 AWG1.52V1.27%0.6333%OK
250 kcmil1.29V1.07%0.5365%OK
300 kcmil1.07V0.8937%0.4469%OK
350 kcmil0.9175V0.7646%0.3823%OK
500 kcmil0.645V0.5375%0.2688%OK

Frequently Asked Questions

3/0 AWG carrying 25A over 500ft has a 1.92V drop (1.6% on 120V). Reference: 0.7979% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.6%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7979% on 240V versus 1.6% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.