What Is the Voltage Drop for 6 AWG at 11A and 125 Feet?

Running 11A through 6 AWG copper for 125 feet on a single-phase / DC circuit produces a 1.35-volt drop. On a 120V source that is 1.13%; on 240V it is 0.5626%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

6 AWG, 11A, 125ft · single-phase / DC
1.35 V drop (1.13% on 120V)
On 120V circuit1.13%
On 240V circuit0.5626%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
1.35V (1.13%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 11 × 0.491) ÷ 1000 = 1.35 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.35 ÷ 120) × 100 = 1.13%
On 240V: (1.35 ÷ 240) × 100 = 0.5626%

How This Estimate Changes with Run Length and Gauge

Gauge Check

6 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 11A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2701V0.225%0.1125%OK
50ft0.5401V0.4501%0.225%OK
75ft0.8101V0.6751%0.3376%OK
100ft1.08V0.9002%0.4501%OK
150ft1.62V1.35%0.6751%OK
200ft2.16V1.8%0.9002%OK
300ft3.24V2.7%1.35%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 11A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 11A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG1.35V1.13%0.5626%OK
4 AWG0.847V0.7058%0.3529%OK
3 AWG0.6738V0.5615%0.2807%OK
2 AWG0.5335V0.4446%0.2223%OK
1 AWG0.4235V0.3529%0.1765%OK
1/0 AWG0.3355V0.2796%0.1398%OK

Frequently Asked Questions

6 AWG carrying 11A over 125ft has a 1.35V drop (1.13% on 120V). Reference: 0.5626% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5626% on 240V versus 1.13% on 120V.
On 120V, this run sits at 1.13%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
6 AWG already sits within the 3% branch-circuit drop target at these inputs (1.13% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.