6 AWG at 80A and 200 Feet: Ampacity-Invalid Reference Calculation

Reference voltage-drop calculation only. 6 AWG is NEC-capped at 65A branch-circuit OCP per NEC 240.4(D) (75°C ampacity 65A), so 80A on this gauge fails the ampacity check before voltage drop ever enters the conversation. Do not use the number below as an install spec. The 15.71-volt reference drop at 80A through 6 AWG for 200 feet is still a valid I×R calculation across the conductor, which is why this page renders it, but it is a reference-only figure and not a permission slip to run that current on that gauge.

6 AWG, 80A, 200ft · single-phase / DC · reference only, ampacity-invalid
15.71 V drop (13.09% on 120V)
On 120V circuit13.09%
On 240V circuit6.55%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
15.71V (13.09%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 80 × 0.491) ÷ 1000 = 15.71 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (15.71 ÷ 120) × 100 = 13.09%
On 240V: (15.71 ÷ 240) × 100 = 6.55%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

6 AWG can't carry the 80A load in the first place, its branch-circuit OCP cap is 65A under typical conditions. The smallest gauge in our table that clears both the ampacity cap and the 3% drop target at these inputs is 2/0 AWG. Run the full wire-size calculator for run length, material, and drop-target variations.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 80A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.96V1.64%0.8183%OK
50ft3.93V3.27%1.64%Caution
75ft5.89V4.91%2.46%Caution
100ft7.86V6.55%3.27%Past 5%
150ft11.78V9.82%4.91%Past 5%
200ft15.71V13.09%6.55%Past 5%
300ft23.57V19.64%9.82%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 80A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 80A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG9.86V8.21%4.11%Past 5%
3 AWG7.84V6.53%3.27%Past 5%
2 AWG6.21V5.17%2.59%Past 5%
1 AWG4.93V4.11%2.05%Caution
1/0 AWG3.9V3.25%1.63%Caution
2/0 AWG3.09V2.58%1.29%OK
3/0 AWG2.45V2.04%1.02%OK
4/0 AWG1.95V1.62%0.8107%OK
250 kcmil1.65V1.37%0.6867%OK
300 kcmil1.37V1.14%0.572%OK
350 kcmil1.17V0.9787%0.4893%OK
500 kcmil0.8256V0.688%0.344%OK
750 kcmil0.5472V0.456%0.228%OK

Frequently Asked Questions

6 AWG carrying 80A over 200ft has a 15.71V drop (13.09% on 120V), but 6 AWG is NEC-capped at 65A branch-circuit OCP per NEC 240.4(D), so 80A on 6 AWG is ampacity-invalid and the drop figure above is a reference calculation only, not an install spec. Reference: 6.55% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
This run is at 13.09% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 80A over 200ft on 120V, the smallest gauge in our table that clears it is 2/0 AWG at 2.58%. Going up one size from 6 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 6.55% on 240V versus 13.09% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.