6 AWG at 80A and 200 Feet: Ampacity-Invalid Reference Calculation
Reference voltage-drop calculation only. 6 AWG is NEC-capped at 65A branch-circuit OCP per NEC 240.4(D) (75°C ampacity 65A), so 80A on this gauge fails the ampacity check before voltage drop ever enters the conversation. Do not use the number below as an install spec. The 15.71-volt reference drop at 80A through 6 AWG for 200 feet is still a valid I×R calculation across the conductor, which is why this page renders it, but it is a reference-only figure and not a permission slip to run that current on that gauge.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge That Meets the 3% Target
6 AWG can't carry the 80A load in the first place, its branch-circuit OCP cap is 65A under typical conditions. The smallest gauge in our table that clears both the ampacity cap and the 3% drop target at these inputs is 2/0 AWG. Run the full wire-size calculator for run length, material, and drop-target variations.
Impact of Distance
Voltage drop is proportional to distance. Here is 6 AWG at 80A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 1.96V | 1.64% | 0.8183% | OK |
| 50ft | 3.93V | 3.27% | 1.64% | Caution |
| 75ft | 5.89V | 4.91% | 2.46% | Caution |
| 100ft | 7.86V | 6.55% | 3.27% | Past 5% |
| 150ft | 11.78V | 9.82% | 4.91% | Past 5% |
| 200ft | 15.71V | 13.09% | 6.55% | Past 5% |
| 300ft | 23.57V | 19.64% | 9.82% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 80A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 80A load are listed, since thinner gauges would fail the ampacity check before drop even matters.
| Gauge | Drop (V) | % on 120V | % on 240V | 3% Target (120V) |
|---|---|---|---|---|
| 4 AWG | 9.86V | 8.21% | 4.11% | Past 5% |
| 3 AWG | 7.84V | 6.53% | 3.27% | Past 5% |
| 2 AWG | 6.21V | 5.17% | 2.59% | Past 5% |
| 1 AWG | 4.93V | 4.11% | 2.05% | Caution |
| 1/0 AWG | 3.9V | 3.25% | 1.63% | Caution |
| 2/0 AWG | 3.09V | 2.58% | 1.29% | OK |
| 3/0 AWG | 2.45V | 2.04% | 1.02% | OK |
| 4/0 AWG | 1.95V | 1.62% | 0.8107% | OK |
| 250 kcmil | 1.65V | 1.37% | 0.6867% | OK |
| 300 kcmil | 1.37V | 1.14% | 0.572% | OK |
| 350 kcmil | 1.17V | 0.9787% | 0.4893% | OK |
| 500 kcmil | 0.8256V | 0.688% | 0.344% | OK |
| 750 kcmil | 0.5472V | 0.456% | 0.228% | OK |