What Is the Voltage Drop for 8 AWG at 8A and 250 Feet?

8 AWG copper carrying 8 amps over 250 feet on a single-phase / DC circuit drops 3.11 volts (2.59% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

8 AWG, 8A, 250ft · single-phase / DC
3.11 V drop (2.59% on 120V)
On 120V circuit2.59%
On 240V circuit1.3%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
3.11V (2.59%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 8 × 0.778) ÷ 1000 = 3.11 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.11 ÷ 120) × 100 = 2.59%
On 240V: (3.11 ÷ 240) × 100 = 1.3%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 8A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3112V0.2593%0.1297%OK
50ft0.6224V0.5187%0.2593%OK
75ft0.9336V0.778%0.389%OK
100ft1.24V1.04%0.5187%OK
150ft1.87V1.56%0.778%OK
200ft2.49V2.07%1.04%OK
300ft3.73V3.11%1.56%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 8A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 8A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG3.11V2.59%1.3%OK
6 AWG1.96V1.64%0.8183%OK
4 AWG1.23V1.03%0.5133%OK
3 AWG0.98V0.8167%0.4083%OK
2 AWG0.776V0.6467%0.3233%OK
1 AWG0.616V0.5133%0.2567%OK

Frequently Asked Questions

8 AWG carrying 8A over 250ft has a 3.11V drop (2.59% on 120V). Reference: 1.3% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.59%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.3% on 240V versus 2.59% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.