How Many Amps Is 1,380 Watts at 100V?

1,380 watts at 100V draws 13.8 amps on an AC single-phase resistive circuit. Reactive or motor loads at the same real power draw more current than the resistive figure because of the power-factor penalty.

At 13.8A, the NEC 210.19(A) continuous-load sizing math (125% of the load, equivalently 80% of the breaker rating) points to a 20A breaker as the smallest standard size that covers this load continuously. A 15A breaker is the smallest standard size the raw current fits under, but it is non-continuous-only at this load.

1,380 watts at 100V
13.8 Amps
1,380 watts equals 13.8 amps at 100 volts (AC single-phase, PF 1.0 resistive)
DC13.8 A
13.8

Assumes an AC single-phase resistive load at PF 1.0. Typing a commercial L-L voltage (208/400/480V) re-routes the result to three-phase; 277V stays on single-phase because it's the L-N lighting leg of a 480Y/277V wye; 12/24V re-routes to DC.

Formulas

DC: Watts to Amps

I(A) = P(W) ÷ V(V)

1,380 ÷ 100 = 13.8 A

AC Single Phase (PF = 0.85)

I(A) = P(W) ÷ (PF × V(V))

1,380 ÷ (0.85 × 100) = 1,380 ÷ 85 = 16.24 A

Circuit Sizing

Breaker Sizing

NEC 240.6(A) standard ampere ratings for branch-circuit and feeder breakers start at 15, 20, 25, 30, 35, 40, 45, and 50A and continue at 60A and above for feeder and large-appliance circuits. At 13.8A, the smallest standard breaker the raw current fits under is 15A, but that breaker only covers 15A non-continuously; NEC 210.19(A) requires conductor and OCP sized at 125% of any continuous load (equivalently 80% of breaker rating), so for a continuous load the smallest compliant breaker is 20A. Final selection still depends on the equipment nameplate, whether the load is continuous, conductor ampacity, and local code.

Breaker SizeMax Continuous Load (80%)Status for 13.8A
15A12ANon-continuous only
20A16AOK for continuous
25A20AOK for continuous
30A24AOK for continuous
35A28AOK for continuous
40A32AOK for continuous
45A36AOK for continuous
50A40AOK for continuous

Energy Cost

Running 1,380W costs approximately $0.23 per hour at the US average rate of $0.17/kWh (rates last reviewed April 2026). That is $1.88 for 8 hours or about $56.30 per month. See detailed cost breakdown.

AC Conversion Detail

The DC baseline for 1,380W at 100V is 13.8A. On an AC circuit with a power factor of 0.85, the current rises to 16.24A because reactive current flows alongside the real-power current.

Circuit TypeFormulaResult
DC1,380 ÷ 10013.8 A
AC Single Phase (PF 0.85)1,380 ÷ (100 × 0.85)16.24 A

Power Factor Reference

Power factor is the main reason 1,380W draws more current on AC than DC. At PF 1.0 (pure resistive, like a heater), the load pulls 13.8A at 100V on the single-phase basis the rest of the page uses. At PF 0.80 (typical induction motor), the same 1,380W pulls 17.25A. That is an extra 3.45A just to overcome the reactive component. Use the typical values below as a starting point, not for precise engineering calculations.

Load TypeTypical PF1,380W at 100V (single-phase)
Resistive (heaters, incandescent)113.8 A
Fluorescent lamps0.9514.53 A
LED lighting0.915.33 A
Synchronous motors0.915.33 A
Typical mixed loads0.8516.24 A
Induction motors (full load)0.817.25 A
Computers (without PFC)0.6521.23 A
Induction motors (no load)0.3539.43 A

Other Wattages at 100V

WattsAC 1Φ Amps PF 1.0 resistiveAC 1Φ Amps PF 0.85 motor
400W4A4.71A
450W4.5A5.29A
500W5A5.88A
600W6A7.06A
700W7A8.24A
750W7.5A8.82A
800W8A9.41A
900W9A10.59A
1,000W10A11.76A
1,100W11A12.94A
1,200W12A14.12A
1,300W13A15.29A
1,400W14A16.47A
1,500W15A17.65A
1,600W16A18.82A
1,700W17A20A
1,800W18A21.18A
1,900W19A22.35A
2,000W20A23.53A
2,200W22A25.88A

Frequently Asked Questions

1,380W at 100V draws 13.8 amps on AC single-phase at PF 1.0 (resistive). For comparison at the same voltage: 13.8A on DC, 16.24A on AC single-phase at PF 0.85. Actual current depends on the load's power factor.
Yes. Higher voltage means lower current for the same real power. 1,380W at 100V draws 13.8A on AC single-phase at PF 1.0 (resistive). As a resistive-baseline comparison at the same wattage, a DC or PF 1.0 load would draw 27.6A at 50V and 6.9A at 200V. Doubling the voltage halves the current and also halves the I²R losses in the conductors.
At the US residential average of $0.17/kWh (last reviewed April 2026), 1,380W costs $0.23 per hour and $1.88 for 8 hours. Rates vary by utility and time of day.
For resistive loads (heaters, incandescent bulbs, electric kettles) use PF 1.0. For motors, use 0.80. For mixed office/residential use 0.85. For computers and LED arrays the effective PF can be 0.65 or lower. Power factor only applies to AC.
At 13.8A the load sits within NEC 210.19(A)'s 80% continuous-load allowance on a 120V/15A circuit (1,440W continuous target). A dedicated 20A circuit gives more headroom if other loads share the wiring.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.